Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 12 (rPDU). 3 (rPDUOutlet). 4 (rPDUOutletConfig). 3 (rPDUOutletConfigMonitoredTable). 1 (rPDUOutletConfigMonitoredEntry). 5 (rPDUOutletConfigMonitoredNearOverloadThreshold)
OID : 1.3.6.1.4.1.318.1.1.12.3.4.3.1.5
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. rPDU. rPDUOutlet. rPDUOutletConfig. rPDUOutletConfigMonitoredTable. rPDUOutletConfigMonitoredEntry. rPDUOutletConfigMonitoredNearOverloadThreshold
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.12.3.4.3.1.5
Module PowerNet-MIB (APC)
NomrPDUOutletConfigMonitoredNearOverloadThreshold
Accesreadwrite
Statusmandatory
DescriptionA threshold that indicates the power consumption of the load is nearing an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than the value returned by the rPDUOutletConfigMonitoredLowLoadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDUOutletConfigMonitoredOverloadThreshold OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU.
SyntaxeInteger32