MIB Discovery
1930 modules enregistrés
Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 15 (xPDU). 4 (xPDUCircuitBreakers). 2 (xPDUBranchBreakers). 3 (xPDUBranchBreakerTable). 1 (xPDUBranchBreakerEntry). 2 (xPDUBranchBreakerRating)
OID : 1.3.6.1.4.1.318.1.1.15.4.2.3.1.2
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. xPDU. xPDUCircuitBreakers. xPDUBranchBreakers. xPDUBranchBreakerTable. xPDUBranchBreakerEntry. xPDUBranchBreakerRating
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.15.4.2.3.1.2
Module PowerNet-MIB (APC)
NomxPDUBranchBreakerRating
Accesreadwrite
Statusmandatory
DescriptionIndicates current rating of this breaker. 0=Breaker is not present. 1=Earth leakage connection. 2=Neutral connection. A value greater than 2 indicates breaker current rating in Amps. A value above 60 Amp will signify a remote feed. The xPDUBranchBreakerRDPFeed OID will indicate which breakers are configured as a remote drop. Note: When setting branch circuit thresholds/ratings for an entry, all positions tied (see the xPDUBranchBreakerTieIndicator OID) to this entry will inherit the new threshold/rating.
SyntaxeInteger32