| OID | 1.3.6.1.4.1.318.1.1.13.1.3.7.1.9 |
| Module | PowerNet-MIB (APC) |
| Nom | airFMGroupFailoverSysCommLost |
| Acces | readwrite |
| Status | mandatory |
| Description | Enabling this OID will cause the system to enter a failure state if the system has lost comm. Once in the failure state, environmental control ceases for the system, and the blowers enter the Idle Blower Operation mode. A value of notApplicable indicates that this alarm does not apply to this device due to its configuration. |
| Syntaxe | Enumeration (1-notApplicable, 2-disable, 3-enable) |