Description | The type of traps which will be sent to the
requesting host; individual trap receivers will have
individual values for this variable. The additional
variables in types (3) and (4) are useful for determining
which UPS is the source on multi-port network adapters,
and for getting additional descriptive information.
Types (1) through (4) are all SNMP version 1 trap PDUs.
Values are:
(1) stnd: Traps as defined in the Standard UPS MIB (RFC1628)
and Generic (MIB II) traps as defined in RFC 1215.
(2) xups: xupsTrapDefined Traps as defined in the PowerMIB
and Generic (MIB II) traps as defined in RFC 1215.
(3 Deprecated) stndPlus: same as stnd plus variables from the interface
group and, where appropriate, xupsTrapMessage.
(4 Deprecated) xupsPlus: xupsTrapPortN Traps (same as xups plus
variables from the interface group) and,
for authFail, xupsTrapMessage.
(5 pxg: Traps as defined in the Power Xpert Gateway MIB
(PXG-MIB). |