OID | 1.3.6.1.2.1.33.1.2.1 |
Module | UPS-MIB (MGE) |
Nom | upsBatteryStatus |
Acces | readonly |
Status | mandatory |
Description | The indication of the capacity remaining in the UPS
system's batteries. A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output). |
Syntaxe | Enumeration (1-unknown, 2-batteryNormal, 3-batteryLow, 4-batteryDepleted) |
Module | UPS-MIB (ietf) |
Nom | upsBatteryStatus |
Acces | readonly |
Status | current |
Description | The indication of the capacity remaining in the UPS
system's batteries. A value of batteryNormal
indicates that the remaining run-time is greater than
upsConfigLowBattTime. A value of batteryLow indicates
that the remaining battery run-time is less than or
equal to upsConfigLowBattTime. A value of
batteryDepleted indicates that the UPS will be unable
to sustain the present load when and if the utility
power is lost (including the possibility that the
utility power is currently absent and the UPS is
unable to sustain the output). |
Syntaxe | Enumeration (1-unknown, 2-batteryNormal, 3-batteryLow, 4-batteryDepleted) |