MIB Discovery
1930 modules enregistrés
Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 1 (ups). 12 (upsOutletGroups). 2 (upsOutletGroupConfig). 2 (upsOutletGroupConfigTable). 1 (upsOutletGroupConfigEntry). 11 (upsOutletGroupConfigLoadShedControlRuntimeRemaining)
OID : 1.3.6.1.4.1.318.1.1.1.12.2.2.1.11
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. ups. upsOutletGroups. upsOutletGroupConfig. upsOutletGroupConfigTable. upsOutletGroupConfigEntry. upsOutletGroupConfigLoadShedControlRuntimeRemaining
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.1.12.2.2.1.11
Module PowerNet-MIB (APC)
NomupsOutletGroupConfigLoadShedControlRuntimeRemaining
Accesreadwrite
Statusmandatory
DescriptionConfigures whether the outlet group will load shed (turn off) when the UPS is on battery and the remaining runtime is less than the upsOutletGroupConfigLoadShedRuntimeRemaining OID setting. The settings for upsOutletGroupConfigLoadShedControlSkipOffDelay and upsOutletGroupConfigLoadShedControlAutoRestart are valid for this load shed condition.
SyntaxeEnumeration (1-upsOutletGroupConfigDisableRuntimeRemainingLoadShed, 2-upsOutletGroupConfigEnableRuntimeRemainingLoadShed)