OID | 1.3.6.1.4.1.318.1.1.1.2.3.10.2.1.10 |
Module | PowerNet-MIB (APC) |
Nom | upsHighPrecBatteryPackCartridgeStatus |
Acces | readonly |
Status | mandatory |
Description | The battery cartridge status. bit 0 Disconnected bit 1 Overvoltage bit 2 NeedsReplacement bit 3 OvertemperatureCritical bit 4 Charger bit 5 TemperatureSensor bit 6 BusSoftStart bit 7 OvertemperatureWarning bit 8 GeneralError bit 9 Communication bit 10 DisconnectedFrame bit 11 FirmwareMismatch |
Syntaxe | OctetString |