OID | 1.3.6.1.4.1.318.1.1.10.2.3.2.1.14 |
Module | PowerNet-MIB (APC) |
Nom | iemStatusProbeMinHumidViolation |
Acces | readonly |
Status | mandatory |
Description | The minimum humidity violation status of the probe humidity
reading. This OID will show a minTempViolation(2)
if the current humidity reading shown in the
'iemStatusProbeCurrentHumid' OID is less than or equal to
the minimum humidity threshold value, the
'iemConfigProbeMinHumidThreshold' OID, and the value of the
'iemConfigProbeMinHumidEnable' OID is enabled. Otherwise it will
show noViolation(1). If the 'iemConfigProbeMinHumidEnable' OID is
disabled, this OID will show disabled(3). |
Syntaxe | Enumeration (1-noViolation, 2-minHumidViolation, 3-disabled) |