OID | 1.3.6.1.4.1.318.1.1.10.3.12.13 |
Module | PowerNet-MIB (APC) |
Nom | emsStatusHardwareStatus |
Acces | readonly |
Status | mandatory |
Description | The status of the EMS hardware. This integer should be interpreted as a bit map, with each bit representing the presence or absence of a specific hardware error condition. 0 indicates there are no error conditions detected in the EMS hardware. 1 indicates a Current Limit error condition related to the Alink port. 2 indicates incorrect hardware is plugged into an EMS port. 3 indicates that both of these error conditions are present. |
Syntaxe | Integer32 |