OID | 1.3.6.1.4.1.318.1.1.12.2.4.1.1.4 |
Module | PowerNet-MIB (APC) |
Nom | rPDULoadBankConfigOverloadThreshold |
Acces | readwrite |
Status | mandatory |
Description | A threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the rPDULoadBankConfigNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadDevMaxBankLoad OID. |
Syntaxe | Integer32 |