1930 modules enregistrés
Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 12 (rPDU). 3 (rPDUOutlet). 3 (rPDUOutletControl). 1 (rPDUOutletControlTable). 1 (rPDUOutletControlEntry). 4 (rPDUOutletControlOutletCommand)
OID : 1.3.6.1.4.1.318.1.1.12.3.3.1.1.4
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. rPDU. rPDUOutlet. rPDUOutletControl. rPDUOutletControlTable. rPDUOutletControlEntry. rPDUOutletControlOutletCommand
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.12.3.3.1.1.4
Module PowerNet-MIB (APC)
NomrPDUOutletControlOutletCommand
Accesreadwrite
Statusmandatory
DescriptionGetting this variable will return the outlet state. If the outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. Setting this variable to immediateOn (1) will immediately turn the outlet on. Setting this variable to immediateOff (2) will immediately turn the outlet off. Setting this variable to immediateReboot (3) will immediately reboot the outlet. Setting this variable to delayedOn (4) will turn the outlet on after the rPDUOutletConfigPowerOnTime OID time has elapsed. Setting this variable to delayedOff (5) will turn the outlet off after the rPDUOutletConfigPowerOffTime OID time has elapsed. Setting this variable to delayedReboot (6) will cause the Switched Rack PDU to perform a delayedOff command, wait the rPDUOutletConfigRebootDuration OID time, and then perform a delayedOn command. Setting this variable to cancelPendingCommand (7) will cause any pending command to this outlet to be canceled.
SyntaxeEnumeration (1-immediateOn, 2-immediateOff, 3-immediateReboot, 4-delayedOn, 5-delayedOff, 6-delayedReboot, 7-cancelPendingCommand)