OID | 1.3.6.1.4.1.318.1.1.12.3.4.3.1.4 |
Module | PowerNet-MIB (APC) |
Nom | rPDUOutletConfigMonitoredLowLoadThreshold |
Acces | readwrite |
Status | mandatory |
Description | A threshold that indicates the power consumption of the load is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps effectively disables this warning. Maximum value must be less than the value returned by the rPDUOutletConfigMonitoredNearOverloadThreshold OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU. |
Syntaxe | Integer32 |