MIB Discovery
1930 modules enregistrés
Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 12 (rPDU). 3 (rPDUOutlet). 4 (rPDUOutletConfig). 3 (rPDUOutletConfigMonitoredTable). 1 (rPDUOutletConfigMonitoredEntry). 6 (rPDUOutletConfigMonitoredOverloadThreshold)
OID : 1.3.6.1.4.1.318.1.1.12.3.4.3.1.6
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. rPDU. rPDUOutlet. rPDUOutletConfig. rPDUOutletConfigMonitoredTable. rPDUOutletConfigMonitoredEntry. rPDUOutletConfigMonitoredOverloadThreshold
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.12.3.4.3.1.6
Module PowerNet-MIB (APC)
NomrPDUOutletConfigMonitoredOverloadThreshold
Accesreadwrite
Statusmandatory
DescriptionA threshold that indicates the power consumption of the load has entered an overload condition. It is represented in Amps. A warning will be issued when the load is greater than or equal to the threshold value. Minimum value must be greater than or equal to the value returned by the rPDUOutletConfigMonitoredNearOverloadThreshold OID. Maximum value must be less than or equal to the value returned by the rPDULoadDevMaxOutletLoad OID. 0 will be returned if the unit is not Outlet Monitored Rack PDU.
SyntaxeInteger32