OID | 1.3.6.1.4.1.318.1.1.12.5.2.1.3 |
Module | PowerNet-MIB (APC) |
Nom | rPDUStatusBankState |
Acces | readonly |
Status | mandatory |
Description | Getting this OID will return the bank load state. bankLoadNormal(1) indicates that the bank is operating properly within the rPDULoadBankConfigLowLoadThreshold and rPDULoadBankConfigNearOverloadThreshold OID values. bankLoadLow(2) indicates that the bank load has dropped below the rPDULoadBankConfigLowLoadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. bankLoadNearOverload(3) indicates that the bank load is greater than or equal to the rPDULoadBankConfigNearOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. bankLoadOverload(4) indicates that the bank load is greater than or equal to the rPDULoadBankConfigOverloadThreshold OID value. An SNMP trap will occur when this state is entered or cleared. |
Syntaxe | Enumeration (1-bankLoadNormal, 2-bankLoadLow, 3-bankLoadNearOverload, 4-bankLoadOverload) |