OID | 1.3.6.1.4.1.318.1.1.13.1.4.5.16 |
Module | PowerNet-MIB (APC) |
Nom | airFMSysCoilFluidActivThreshC |
Acces | readwrite |
Status | mandatory |
Description | The minimum coolant temperature required to use the optional MultiCool or Economizer coil. Measured in tenths of degrees Celsius. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. |
Syntaxe | Integer32 |