| OID | 1.3.6.1.4.1.318.1.1.13.1.4.5.19 |
| Module | PowerNet-MIB (APC) |
| Nom | airFMSysCoilFluidActivDeadbandF |
| Acces | readwrite |
| Status | mandatory |
| Description | The controller will disengage the MultiCool or Economizer coil when the coolant temperature reaches the coil fluid temperature activation threshold plus the deadband. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. |
| Syntaxe | Integer32 |