OID | 1.3.6.1.4.1.318.1.1.13.1.4.8.6 |
Module | PowerNet-MIB (APC) |
Nom | airFMSysReheatDeadbandF |
Acces | readwrite |
Status | mandatory |
Description | The temperature range that controls output when the selected control sensor temperature is below the setpoint. At the bottom of this range, the reheat mode outputs at 100%. The deadband does not apply to PID-controlled modes. Measured in tenths of degrees Fahrenheit. A value of -2147483648 indicates that this OID does not apply to this device due to its configuration. |
Syntaxe | Integer32 |