OID | 1.3.6.1.4.1.318.1.1.15.4.2.3.1.2 |
Module | PowerNet-MIB (APC) |
Nom | xPDUBranchBreakerRating |
Acces | readwrite |
Status | mandatory |
Description | Indicates current rating of this breaker. 0=Breaker is not present. 1=Earth leakage connection. 2=Neutral connection. A value greater than 2 indicates breaker current rating in Amps. A value above 60 Amp will signify a remote feed. The xPDUBranchBreakerRDPFeed OID will indicate which breakers are configured as a remote drop. Note: When setting branch circuit thresholds/ratings for an entry, all positions tied (see the xPDUBranchBreakerTieIndicator OID) to this entry will inherit the new threshold/rating. |
Syntaxe | Integer32 |