MIB Discovery
1930 modules enregistrés
Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 15 (xPDU). 4 (xPDUCircuitBreakers). 2 (xPDUBranchBreakers). 3 (xPDUBranchBreakerTable). 1 (xPDUBranchBreakerEntry). 4 (xPDUBranchBreakerTieIndicator)
OID : 1.3.6.1.4.1.318.1.1.15.4.2.3.1.4
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. xPDU. xPDUCircuitBreakers. xPDUBranchBreakers. xPDUBranchBreakerTable. xPDUBranchBreakerEntry. xPDUBranchBreakerTieIndicator
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.15.4.2.3.1.4
Module PowerNet-MIB (APC)
NomxPDUBranchBreakerTieIndicator
Accesreadwrite
Statusmandatory
DescriptionIndicates whether or not the breaker in this position is logically associated with the breaker immediately below it. This setting is used grouping the breakers feeding a multi-pole branch circuit. Note: When setting an entry's branch breaker tie indicator to breakerTied, all the positions that are tied to this breaker will take on the rating and thresholds for this entry of the table.
SyntaxeEnumeration (1-breakerUnTied, 2-breakerTied)