| OID | 1.3.6.1.4.1.318.1.1.22.4.1.9 |
| Module | PowerNet-MIB (APC) |
| Nom | isxModularDistSysOutputVoltageThresholdMax |
| Acces | readwrite |
| Status | mandatory |
| Description | When the line-to-neutral voltage of any phase exceeds this value a critical alarm will exist. Specified as a percent of the nominal voltage, isxModularDistSysOutputVoltageNominalLineToNeutral. A value of -1 indicates that the threshold is not available in the device. |
| Syntaxe | Integer32 |