MIB Discovery
1930 modules enregistrés
Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 5 (masterswitchVM). 3 (sPDUMasterConfigVM). 2 (sPDUMasterConfigVMTable). 1 (sPDUMasterConfigVMEntry). 7 (sPDUMasterConfigVMOverloadRestriction)
OID : 1.3.6.1.4.1.318.1.1.5.3.2.1.7
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. masterswitchVM. sPDUMasterConfigVM. sPDUMasterConfigVMTable. sPDUMasterConfigVMEntry. sPDUMasterConfigVMOverloadRestriction
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.5.3.2.1.7
Module PowerNet-MIB (APC)
NomsPDUMasterConfigVMOverloadRestriction
Accesreadwrite
Statusmandatory
DescriptionThis OID controls the behavior of the MasterSwitch VM when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will always allow the outlets to turn on. Setting this OID to restrictOnWarning (2) will not allow outlets to turn on if the sPDUMasterConfigVMHighLoadWarningThreshold OID is exceeded. Setting this OID to restrictOnOverload (3) will not allow outlets to turn on if the MasterSwitch Vm is in an overload condition.
SyntaxeEnumeration (1-alwaysAllowTurnON, 2-restrictOnWarning, 3-restrictOnOverload)