OID | 1.3.6.1.4.1.318.1.1.5.5.1.1.5 |
Module | PowerNet-MIB (APC) |
Nom | sPDUOutletControlVMOutletCommand |
Acces | readwrite |
Status | mandatory |
Description | Getting this variable will return the outlet state. If
the outlet is on, the immediateOnVM (1) value will be returned.
If the outlet is off, the immediateOffVM (2) value will be
returned.
Setting this variable to immediateOnVM (1) will immediately turn the outlet on.
Setting this variable to immediateOffVM (2) will immediately turn the outlet off.
Setting this variable to immediateRebootVM (3) will immediately reboot the outlet.
Setting this variable to delayedOnVM (4) will turn the outlet on
after the sPDUOutletConfigVMPowerOnTime OID time has elapsed.
Setting this variable to delayedOffVM (5) will turn the outlet off
after the sPDUOutletConfigVMPowerOffTime OID time has elapsed.
Setting this variable to delayedRebootVM (6) will cause the
MasterSwitch VM to perform a delayedOffVM command, wait the
sPDUOutletConfigVMRebootDuration OID time, and then perform the
immediateOnVM command.
Setting this variable to cancelPendingCommandVM (7) will cause any
pending command to this outlet to be canceled. |
Syntaxe | Enumeration (1-immediateOnVM, 2-immediateOffVM, 3-immediateRebootVM, 4-delayedOnVM, 5-delayedOffVM, 6-delayedRebootVM, 7-cancelPendingCommandVM) |