MIB Discovery
1930 modules enregistrés
Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 7 (dcDM3). 2 (dm3Config). 1 (dm3ConfigSystem). 8 (dm3ConfigSysRemoteAccess)
OID : 1.3.6.1.4.1.318.1.1.7.2.1.8
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. dcDM3. dm3Config. dm3ConfigSystem. dm3ConfigSysRemoteAccess
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.7.2.1.8
Module PowerNet-MIB (APC)
Nomdm3ConfigSysRemoteAccess
Accesreadwrite
Statusmandatory
DescriptionThis OID is used to disable remote write access to the power plant. Setting this OID to accessEnabled (1) will have no affect. Setting this OID to accessDisabled (2) will disable the ability to remotely configure the DC powerplant. Once remote access is disabled, it can only be restored from the front panel of the DC power plant.
SyntaxeEnumeration (1-accessEnabled, 2-accessDisabled)