MIB Discovery
1930 modules enregistrés
Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 7 (dcDM3). 2 (dm3Config). 4 (dm3ConfigPowerModules). 2 (dm3ConfigConverter). 2 (dm3ConfigConvAlarms). 12 (dm3ConfigConvHwVoltAlarm)
OID : 1.3.6.1.4.1.318.1.1.7.2.4.2.2.12
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. dcDM3. dm3Config. dm3ConfigPowerModules. dm3ConfigConverter. dm3ConfigConvAlarms. dm3ConfigConvHwVoltAlarm
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.7.2.4.2.2.12
Module PowerNet-MIB (APC)
Nomdm3ConfigConvHwVoltAlarm
Accesreadwrite
Statusmandatory
DescriptionFor the Converter Voltage Alarm (indicating voltage outside realistic limits, or a possible measurement fault); Setting this OID to alarmIgnore (1) results in the alarm condition being ignored. Setting this OID to alarmRelay1 (2) causes relay 1 to be activated for an alarm condition. Setting this OID to alarmRelay2 (3) causes relay 2 to be activated for an alarm condition. Setting this OID to alarmRelay3 (4) causes relay 3 to be activated for an alarm condition. Setting this OID to alarmRelay4 (5) causes relay 4 to be activated for an alarm condition. Setting this OID to alarmRelay5 (6) causes relay 5 to be activated for an alarm condition. Setting this OID to alarmRelay6 (7) causes relay 6 to be activated for an alarm condition. Setting this OID to alarmMinor (8) causes the Minor relay to be activated for an alarm condition. Setting this OID to alarmMajor (9) causes the Major relay to be activated for an alarm condition. Setting this OID to alarmNofN (10) causes the alarm specified in the dm3ConfigConv1ofNAlarm OID to be activated if ONE converter fails in an N+1 system. It causes the alarm specified in the dm3ConfigConv2ofNAlarm OID to be activated if TWO OR MORE converters fail in an N+1 system.
SyntaxeEnumeration (1-alarmIgnore, 2-alarmRelay1, 3-alarmRelay2, 4-alarmRelay3, 5-alarmRelay4, 6-alarmRelay5, 7-alarmRelay6, 8-alarmMinor, 9-alarmMajor, 10-alarmNofN)