OID | 1.3.6.1.4.1.318.1.1.8.4.16.1.3 |
Module | PowerNet-MIB (APC) |
Nom | atsConfigPhaseLowLoadThreshold |
Acces | readwrite |
Status | mandatory |
Description | A threshold that indicates the current drawn is nearing a low consumption condition. It is represented in Amps. A warning will be issued when the load is less than the threshold value. A threshold value of 0 Amps disables this warning. Maximum value must be less than the value returned by the atsConfigPhaseNearOverLoadThreshold OID. |
Syntaxe | Integer32 |