MIB Discovery
1930 modules enregistrés
Chemin
MIX : 1 (iso). 3 (org). 6 (dod). 1 (internet). 4 (private). 1 (enterprises). 318 (apc). 1 (products). 1 (hardware). 8 (automaticTransferSwitch). 4 (atsConfig). 5 (atsConfigTransferVoltageRange)
OID : 1.3.6.1.4.1.318.1.1.8.4.5
TXT : iso. org. dod. internet. private. enterprises. apc. products. hardware. automaticTransferSwitch. atsConfig. atsConfigTransferVoltageRange
Enfants
Pas d'enfants disponibles pour cet OID
Détails
OID1.3.6.1.4.1.318.1.1.8.4.5
Module PowerNet-MIB (APC)
NomatsConfigTransferVoltageRange
Accesreadwrite
Statusmandatory
DescriptionThis variable defines the range of acceptable voltage from a power source. If the voltage measured from the selected input source is not within this range, the Automatic Transfer Switch will switch over (transfer) to the alternate power source.
SyntaxeEnumeration (1-wide, 2-medium, 3-narrow)